Quick Details

  • Place of Origin:Shandong, China (Mainland)

  • Brand Name:Horis

  • Model Number:HT8GF/S--HT500GF/S

  • Output Type:AC Three Phase

  • Speed:1500/1800

  • Frequency:50/60HZ

  • Rated Power:8KW-500KW

  • Rated Voltage:230/415V

  • Rated Current:14.8A-900A

  • engine:Cummins / perkins/ ricardo / lovol / deutz etc

  • alternator:stamford / marathon / qianghui etc

  • trailer:2 wheel or 4 wheel

  • excitation:burshless

  • protection:H

  • short circuit protection:MCCB

  • color:yellow/green/others

  • Phase:One /Three

  • MOQ:1 set

Packaging & Delivery

Packaging Details:wooden case
Delivery Detail:15-30 days

Specifications

1)trailer generator with 2 or 4 wheels
2)work in open air
3)mobile generator with CE & ISO
4)delivery :15-30 days

1.Specifications of trailer generator:


1) Output range:          from 20kW (25kVA) up to 500kW (625kVA)
2) Engine model:         Deutz, Perkins, Steyr and Cummins are produced by joint
ventures in China
3) Alternator model:     GM / MP
4)Cooling :                   Water-cooled
5) Fuel tank:                 8hrs operation base tank
6) Start :                       Key start / auto start
7) Type :                       Sound-proof / weather-proof canopy is optional
8) Specification:            230 / 400V AC, 50Hz / 60Hz, 0.8pF ,3p4w
9) Frequency:               <3%
10) Frequency at stable state:  <0.5%
11) Frequency deviation at instantaneous state:   ≤+10%
12) Frequency return time      ≤3s
13) Voltage deviation at stable state:    ≤±1%
14) Voltage deviation at instantaneous state:   ≤+20%
15) Voltage return time:    ≤4s
16) Voltage modulation:    ≤0.3%

17) Starting system:     DC alternator is used to start engine
18) Short circuit protection: MCCB air switch
19) Cooling system:      combined cooling water tank fitted to meet the
requirement of radiation at ambient temperature 40°C
20) Filter system:         oil, fuel and air filter
21) Accessories:           exhaust elbow, bellow, muffler

2. Standard configuration of gensets


a) Engine: Deutz, Perkins, Steyr, Cummins series produced by joint
ventures in China
b) Engine type: water-cooled, in line four-stoke, Humit cylinder liner,
direct injection
c) Alternator:Stamford / Marathon brushless alternator


3. Control system:
a) Automatic alarm system: the unit has the acousto-optics alarm
system and arrestor for any situation as the start defeat, the water
is over temperature, the oil pulls down, over speed, over load and
over current


b) Operation display:
i) Unit voltage, tri-phase load current and frequency display
ii) Water temperature, oil pressure display
iii) Fuel level, fuel temperature display
iv) Audible and visual alarm lamps and buzzers